Communities

Writing
Writing
Codidact Meta
Codidact Meta
The Great Outdoors
The Great Outdoors
Photography & Video
Photography & Video
Scientific Speculation
Scientific Speculation
Cooking
Cooking
Electrical Engineering
Electrical Engineering
Judaism
Judaism
Languages & Linguistics
Languages & Linguistics
Software Development
Software Development
Mathematics
Mathematics
Christianity
Christianity
Code Golf
Code Golf
Music
Music
Physics
Physics
Linux Systems
Linux Systems
Power Users
Power Users
Tabletop RPGs
Tabletop RPGs
Community Proposals
Community Proposals
tag:snake search within a tag
answers:0 unanswered questions
user:xxxx search by author id
score:0.5 posts with 0.5+ score
"snake oil" exact phrase
votes:4 posts with 4+ votes
created:<1w created < 1 week ago
post_type:xxxx type of post
Search help
Notifications
Mark all as read See all your notifications »
Q&A

Cable voltage rating

+3
−0

I was looking for guidelines of how to select appropriate cables for applications (I am interested in DC), I found IEC 183 standard which talks about high voltage cable selection for AC. Also, the status of the document is shown as withdrawn, so I assume it is not applicable.

I found another document referencing IEC 183

What I see at the bottom of the page: Image_alt_text

U0 = cable nominal voltage between the conductor and the metal covering or earth.

U = cable nominal voltage between the phase conductors.

First question I have is why conductor/earth voltage rating for DC is specified lower at 0.9kV? I would imagine that due to capacitance of the insulating material the total impedance between conductor and whatever is on the other side of insulation is lower, so the rated voltage would be lower. Why isn't that the case, or perhaps the reference is wrong?

My second question is if there are any standards for selecting proper insulation for high voltage DC cables. Is it application dependent as well, such as free air, submerged, vacuum, or medical/military grade etc.? If you could point me to some IEC/IPC standards that mention this I would highly appreciate it.

My last question is the margin for voltage. For capacitors, on an output of 8V power supply we do not place capacitors rated 10V, we leave a bigger margin. What about cables? I read that due to partial discharge cable insulation degrades over time. What is a reasonable margin for insulation rating?

History
Why does this post require moderator attention?
You might want to add some details to your flag.
Why should this post be closed?

1 comment thread

Standards (4 comments)

1 answer

+1
−0

First question I have is why conductor/earth voltage rating for DC is specified lower at 0.9kV?

Imagine two cables running side to side. To get from one cable to the other, an electron would have to cross the insulator twice, but if those two cable ran against a conductive surface (a metal plate or beam, for example), the same electron would only have to cross the insulator once, and since most regulations call for all conductive surfaces to be grounded, there is your conductor-to-earth max voltage.

Half the insulation, half the maximum voltage.

My second question is if there are any standards for selecting proper insulation for high voltage DC cables.

That is taken care of by the cable manufacturer. The designer usually selects their cable from the catalog of reputable manufacturers and distributors, and according to their project's specific requirements. How the manufacturer reaches said requirements is up to them.

[...] we leave a bigger margin. What about cables?

If necessary, this is often called for by the customer through a design specification. The practice is called "derating" and is expressed in percentage. For example, if your design case calls for a 20% derating, you would ensure that a cable rated for 1kV never carries more than 800V (1kV - 20%).

Regarding degradation over time, the reputable manfacturers I mentioned before would supply, along with voltage and current rating, duration of safe operation for specific environment (marine, contact with solvent, vacuum, etc.

In conclusion,when designing/selecting cable, focus on the constraints you have. How the manufacturer manages them is their issue (once again, assuming you use good suppliers).

History
Why does this post require moderator attention?
You might want to add some details to your flag.

0 comment threads

Sign up to answer this question »